Kates FC Valve Automatic Flow Rate Controller

Home » W.A. Kates Flow Controllers » Kates FC Valve Automatic Flow Rate Controller

Kates Flow Rate Controller
Specifications
  • Material of construction: 316SS, others
  • Seals: PTFE, Buna, Viton, others available
  • Max Work Pressure: 6,000psi
  • Max Temperature: 400° F norm - spec. available
  • Accuracy: ± 1-1/2% of setpoint
  • Repeatability: ± 1-1/2% of setpoint
  • Response time: 1-2 seconds
  • Turndown ratio: 25 to 1 (average)
  • Connections: FNPT or ANSI flanged
Materials of Construction
  • All metal wetted parts:
    • 316 stainless steel.
  • Other Available Materials:
    • Hastelloy, PVC
    • Alloy 20, Monel
Typical Applications

Deionized Water, Rotating Seals, Additives/Blending, Nitrogen Blanketing, Natural Gas, Bleaching Systems, Reverse Osmosis, Dynamometers, Ratio Blending, Humidity Control, Heat Exchangers, Cooling Water, Dust Suppression, Aircraft De-icing, Test Cells, Caustics, Acids, Analytical Fast Loops...and hundreds more!

How It Works

Downstream pressure fluctuations are counterbalanced by the internal regulating valve to maintain the SCFM to within 1-1/2% of the flow setting. Variations in upstream pressure and temperature should be minimized due to the compressibility of gases and the corresponding changes in density. The ratings of Kates FC Valves are catalogued in gal/min for purposes of standardization.

Flow rate through an orifice is proportional to the size of the restriction and the differential pressure across it. By combining an adjustable orifice with an internal regulating valve, the Kates controller will maintain a constant pressure drop across the metering orifice.

P1=P2 + Spring Force
Kates Flow Rate Controller For example; if supply pressure (P1) increases, the resulting momentary pressure imbalance immediately moves the impeller downward. This action restricts the valve ports thus increasing orifice backpressure (P2), restoring differential pressure and the flow rate to the original settings. The unit will respond equally as well to an upset in outlet pressure (P3).

request more information

Flow Rate Information